S7 Communication

Introduction​

Using S7-Communication you can access data from Siemens PLCs and the PLC part of SINUMERIK controls. S7-Communication allows you to access Inputs, Output, Merkers, Timers, Counter, and most importantly data blocks (DBs). The protocol works over Profibus, MPI, and Ethernet connections.

Reading data from the PLC​

For S7-300 and S7-400 PLCs you can access the PLC without any special settings in the Step7 project. For S7-1200 and S7-1500 PLCs, you need to set the Data Block you want to access to "Non-optimized access". You also need to disable "Access protection" in the hardware configuration.

PLC addressing​

In S7 communication the PLC is accessed by using the IP address (can also be the IP address of a CP), rack and slot. Rack and slot can be determined from the hardware configuration or the following list:

  • S7-300: Rack 0, Slot 2
  • S7-1200/1500: Rack 0, Slot 1
  • SINUMERIK 840D (PLC): Rack 0, Slot 2

For S7-400 CPUs you need to check the hardware configuration and use the actual rack/slot that the CPU is plugged into.

The data point addresses in VergeLink are slightly different than the variable addresses used on Step 7 or TIA Portal. Here are some examples to guide you in addressing your variables:

AddressStep7 equivalentJS Data typeDescription
DB5,X0.1DB5.DBX0.1BooleanBit 1 of byte 0 of DB 5
DB23,B1 or DB23,BYTE1DB23.DBB1NumberByte 1 (0-255) of DB 23
DB100,C2 or DB100,CHAR2DB100.DBB2StringByte 2 of DB 100 as a Char
DB42,I3 or DB42,INT3DB42.DBW3NumberSigned 16-bit number at byte 3 of DB 42
DB57,WORD4DB57.DBW4NumberUnsigned 16-bit number at byte 4 of DB 57
DB13,DI5 or DB13,DINT5DB13.DBD5NumberSigned 32-bit number at byte 5 of DB 13
DB19,DW6 or DB19,DWORD6DB19.DBD6NumberUnsigned 32-bit number at byte 6 of DB 19
DB21,R7 or DB21,REAL7DB21.DBD7NumberFloating point 32-bit number at byte 7 of DB 21
DB2,S7.10*-StringString of length 10 starting at byte 7 of DB 2
I1.0 or E1.0I1.0 or E1.0BooleanBit 0 of byte 1 of input area
Q2.1 or A2.1Q2.1 or A2.1BooleanBit 1 of byte 2 of output area
M3.2QM3.2BooleanBit 2 of byte 3 of memory area
IB4 or EB4IB4 or EB4NumberByte 4 (0 -255) of input area
QB5 or AB5QB5 or AB5NumberByte 5 (0 -255) of output area
MB6MB6NumberByte 6 (0 -255) of memory area
IC7 or EC7IB7 or EB7StringByte 7 of input area as a Char
QC8 or AC8QB8 or AB8StringByte 8 of output area as a Char
MC9MB9StringByte 9 of memory area as a Char
II10 or EI10IW10 or EW10NumberSigned 16-bit number at byte 10 of input area
QI12 or AI12QW12 or AW12NumberSigned 16-bit number at byte 12 of output area
MI14MW14NumberSigned 16-bit number at byte 14 of memory area
IW16 or EW16IW16 or EW16NumberUnsigned 16-bit number at byte 16 of input area
QW18 or AW18QW18 or AW18NumberUnsigned 16-bit number at byte 18 of output area
MW20MW20NumberUnsigned 16-bit number at byte 20 of memory area
IDI22 or EDI22ID22 or ED22NumberSigned 32-bit number at byte 22 of input area
QDI24 or ADI24QD24 or AD24NumberSigned 32-bit number at byte 24 of output area
MDI26MD26NumberSigned 32-bit number at byte 26 of memory area
ID28 or ED28ID28 or ED28NumberUnsigned 32-bit number at byte 28 of input area
QD30 or AD30QD30 or AD30NumberUnsigned 32-bit number at byte 30 of output area
MD32MD32NumberUnsigned 32-bit number at byte 32 of memory area
IR34 or ER34IR34 or ER34NumberFloating point 32-bit number at byte 34 of input area
QR36 or AR36QR36 or AR36NumberFloating point 32-bit number at byte 36 of output area
MR38MR38NumberFloating point 32-bit number at byte 38 of memory area
DB1,DT0-Date**A timestamp in the DATE_AND_TIME format
DB1,DTZ10-Date**A timestamp in the DATE_AND_TIME format, in UTC
DB2,DTL2-Date**A timestamp in the DTL format
DB2,DTLZ12-Date**A timestamp in the DTL format, in UTC
  • *) Note that strings in S7 PLCs use two extra bytes at start for size & length of the string
  • **) Note that in VergeLink, Date data types are always represented in UTC.

Advanced usage​

Request Batching​

An S7-Communication "client" can specify the amount of data to read from a PLC. This means that VergeLink can intelligently combine your requests for multiple data points into a single request to the PLC. This efficiency gain lowers the impact of the communication load on the PLC cycle time and also allows a higher data rate. To utilize this functionality you need to make sure that the data point addresses are near each other in a single DB.